Explosion-proof lightning protection box HD-D380/220C-XSF

    Online Inquiry
    Click Refresh Verification Code

    Details

    Crate-type explosion-proof power supply lightning protection box

    Electric surge protector of low-voltage distribution system, which is in the form of a box, is explosion proof and designed according to IEC standard. It has invalidation detection indication, overflowing and overheating protection with powerful discharge capacity of lightning current. It's applicable to the protection of buildings' general supply system against lightning. It is very convenient to be maintained. It connects with the circuit in parallel and has no limit to the power of equipment fixed later.


    Model

     

    HD-D380(220)B-XSF60

     

    HD-D380(220)C-XSF40

     

    HD-D380(220)C-XSF20

     

    HD-D380/220C-XSF

    Nominal working voltage Un

     

    380V/220V

     

    380V/220V

     

    380V/220V

     

    380V/220V

    Maximum continuous working voltage Uc

     

    385V/275V

     

    385V/275V

     

    385V/275V

     

    385V/275V

    Nominal discharge currentIn8/20ms

    30KA

     

    20KA

     

    10KA

     

    20KA

    Maximum discharging currentImax8/20ms

    60KA

     

    40KA

     

    20KA

     

    40KA

    Voltagprotection level Up

    2KV

    1.6KV

     

    1.2V

     

    2.1KV

    Prepositive overflowing protection

    63A

     

    32A

     

    16A

     

    32A

    Overall dimension

     

    260×180×85mm

    Response time Ta

     

    25ns

    Operating temperature range Tup

     

    -40℃至+70

    Working order indication

    Green light means normal working, red light is fault indication.

    Section of minimum installed conductor

    6m2 Multi-folded wire

    Explosion proof function

    Available

    Protection grade

    IP20

    Sheathing material

    Metal spraying

    Mode of connection

    Parallel connection

    Protection mode

    4+0/3+1/1+1/2+0


    Ground the null line repeatedly when Long-distance overhead incoming lines enter buildings.

    Plug the power phase line (L) and null line (Ninto corresponding connector of the electric surge protector and make sure it's firm and reliable. Connect the ground terminal of arrester with the ground lead of lightning protection well (recommended earth resistance 4Ω).

    Suggested specification of the lead wire: no less than 6mm2, short and straight.